Three Turnstiles and Barrier Controllers Management Construction Specification

1 Three-turn gate and gate controller wiring specification 1.1 Card reader to controller Card reader to controller cable is recommended to use 8-core shielded twisted pair (3 cores are used for spare), wire diameter greater than 0.3mm, controller The distance to the reader must not exceed 100 meters. It is recommended that it should be within 80 meters.

1.2 Controller-to-computer controller communication lines (including 485/422, 232, and Wiegand, etc.) must use the internationally accepted 8-core shielded twisted pair, which can effectively prevent and shield interference. Wire diameter greater than 0.3mm The bus length is not to exceed 1200. It is recommended to be within 1000 meters. If it is longer, please use other special 485/232 converters or repeaters, and choose a thicker communication cable. The controller GND485-485+ corresponds to the 485 converter GNDTD(A)TD(B) respectively. The communication line is connected in series, do not use star connection or local star connection. If the line is too long and there are too many devices, please Add terminating resistors (with jumper loads) to the last device. Up to 128 controllers can be attached to the bus.

1.3 Three-way switch (control source) to controller The three-way switch to the controller must use a 2-core power cable. The distance from the controller to the three-way switch must not exceed 100 meters and the wire diameter should be greater than 1.0mm. More than 50 meters, with 2.0mm. (If the output 12V power supply has a significant voltage drop, you can fine tune the power supply voltage to 13.6V.

1.4 Routes require that their equipment lines not be strong or electric wire ducts. If it is limited by the environment, if you want to run parallel, you must keep away from more than 50CM.

2 Three-Striking Gate and Barrier Controller Safety Notes 1. Although the controller already has anti-static and anti-lightning design, please ensure that the power supply and chassis are well grounded to protect the circuit from static electricity, lightning, and other equipment. Damaged, stable operation for a long time.

2. Do not hot-swap wiring terminals, or electrified welding operation, the corresponding wiring socket should be unplugged before welding.

3, Do not disassemble the components on the controller, this may cause system information loss or chip damage.

4, connected to the +12V terminal, is conducive to give full play to the performance of the reader, if the reader is +24V power supply, please separate with a linear power supply, and the controller and common ground. Do not introduce +24V into the controller indirectly, otherwise it will cause burnout.

5, the controller can directly plug the UPS uninterruptible power supply to ensure that the system can continue to work after a power outage. The system is equipped with a power-off protection device, even if the power failure system setting information and records are not lost.

6. Try to avoid connecting the controller power supply and other high-current working devices to the same power supply. The operating current of the relay is a maximum of 7A. If you want to control a larger current device, install a more powerful relay. It is better to have a separately controlled switch from the main control power supply box.

7. When installing a remote controller or other additional value-added equipment, be careful not to introduce other electrical signals into the controller.

3 Installation of three-switch brakes and barrier controllers 3.1 Card reader installation The installation height of the card reader is the normal hydropower installation standard (1.45 meters). All external equipment can not be pulled too long to prevent short circuit due to exposure. .

3.2 Controller Installation The controller is easy to maintain and safe when it is installed.

3.3 The isolator is installed in a concealed place and should not be touched.

STAINLESS STEEL PRODUCTS

Stainless steel is a corrosion resistant steel alloy with a minimum of 10% chromium. There are different grades and surface finishes of stainless steel produced to accommodate the environment in which the material will be implemented. Unlike carbon steel, stainless steel does not rust when exposed to air and moisture due to the sufficient amount of chromium present. The chromium creates an invisible passive film of chromium oxide that will not let oxygen attack the surface and prevents rusting of the iron base.

Yuhong Group is a stainless steel manufactory of more than 20 grades of Stainless Steel.

Stainless Steel Seamless Pipe

Stainless Steel Seamless Pipe,Round Stainless Steel Seamless Pipe,Astm Stainless Steel Seamless Pipe

YUHONG GROUP CO.,LIMITED , https://www.jessro-pipefittings.com

This entry was posted in on